DESCATALOGADO ›
Este producto ya no está disponible y ha sido reemplazado por: CS11-L. Algunos accesorios, recambios o servicios pueden todavía estar disponibles.
CS15-L Current Transducer
Services Available

Resumen

The CS15 is a modified version of the CS10 Current Transducer developed specifically for our CR200(X)-series dataloggers. It monitors ac current along an electrical wire for the range of 0.15 A to 125 A.

Leer más

Ventajas y características

  • Ideal applications include motor or generator load conditions, efficiency studies, intermittent fault detection, and rough submetering
  • Sin conexión eléctrica directa al sistema eléctrico

Imágenes

Descripción detallada

The CS15 detects the ac current along an electrical wire using the magnetic field that is generated by that current. It is external to the wire jacket and has no direct electrical connection to the system. This transducer outputs a millivolt signal that our CR200(X)-series dataloggers can directly measure.

The CS15 can be used for motor or generator load condition monitoring, efficiency studies, intermittent fault detection, and rough submetering.

Especificaciones

  • Measurement Range: 0.15 to 125 A
  • Frequency: 50 and 60 Hz
  • Insulation Resistance: 100 MΩ @ 500 Vdc
  • High Potential: 2000 V
  • Rated Current: 125 A
  • Accuracy with 10 Ω Maximum Burden (resistive): typically ±5% of actual value with provided multiplier
  • Operating Temperature Range: -25° to +55°C
  • Case Material: Polypropylene resin
  • Construction: Epoxy encapsulated
  • Outer Diameter: 4.8 cm (1.89 in)
  • Inner Diameter: 1.9 cm (0.75 in)
  • Height: 1.7 cm (0.67 in)

Compatibilidad

Data Logger Considerations

The CS15 was designed specifically for the CR200(X)-series dataloggers. It is measured with the VoltSE instruction. The measurement is generally taken repeatedly inside a measurement loop, then the RMS (root-mean-square) value is determined.


Preguntas frecuentes

Número de FAQs relacionadas con CS15-L: 2

  1. Yes, by connecting the red wire to ground rather than its normal location.
  2. Not directly. If the CS15-L is connected to a CR200(X) datalogger, the datalogger can take the ac measurement and control a solid-state relay based on some threshold within the datalogger program. The solid-state relay can then control other relays, solenoids, or motor starters. (Use of a solid-state relay is preferred because the datalogger can trigger it with a small 5 Vdc mA signal.) For more information, see the “Measurement and Control Peripherals” section of the operator’s manual.